Between SIF-200-GCS and PLC unit |
Communication line |
: |
Based on RS-232C/RS-422A |
|
|
|
Between SIF-200-GCS and GCS-300 |
Communication line |
: |
Based on RS-485 |
|
|
|
Communication method |
: |
Half-duplex start/stop synchronous |
Communication speed |
: |
9600/19200bps by DIP switch |
Data format |
: |
Start bit (1) |
|
|
Data bit (7 or 8) Selectable by DIP switch |
|
|
Parity (even, odd or none) Selectable by DIP switch |
|
|
Stop bit (1 or 2) Selectable by DIP switch |
PLCs corresponding to SIF-200-GCS |
: |
PLCs are selectable by rotary switch. Omron C200H, Mitsubishi A2N,
FX2N, Fuji MICREX-F70 |
Power supply |
: |
100 to 240V AC 50/60Hz |
Power consumption |
: |
Approx. 5VA |
Insulation resistance |
: |
Between [Power terminal and Ground terminal], [Ground terminal
|
|
|
and Digital output], [Power terminal and Digital input], [Digital
|
|
|
output and Ground terminal], [Digital input and Ground
terminal] |
|
|
10Mohm or more, at 500V DC |
Case |
: |
Flame resistant resin, Black |
Mounting |
: |
DIN rail mounting |
Outer dimensions |
: |
48(W)x96(H)x100(D)mm (including round type socket) |
Weight |
: |
Approx. 320g |