Self-balancing
recorder |
SR-200
series |
[Features] |
 |
- Records versatile process volume and monitors by |
high limit alarm and low limit alarm. |
- Analog type with noise resistance |
- Easy handling and maintenance without complex mechanisms |
|
|
Input |
: |
Thermocouple, RTD, DC Current, DC Voltage |
Number of input |
: |
1-pen, 2pen (Pen writing) and 6-point (Dot printing) |
Indicating recording accuracy |
: |
Within ±0.5%FS |
Recording speed |
: |
25, 50, 100mm/h |
Printing interval |
: |
Continuous for pen writing, |
|
|
50Hz; 5 seconds per dot for dot printing |
|
|
60Hz; 4 seconds per dot for dot printing |
Recording chart |
: |
Chart width; 100mm, Length; 10m |
Power supply |
: |
110/220V or 115/230V (must be specified) AC 50/60Hz, |
Options |
: |
High limit alarm (Low limit alarm), Chart speed |
|
|
Hand strap for portable type |
Self-balancing
recorder |
TR-400
series |
[Features] |
 |
- Analog type precise recorder with 180mm chart width which |
records various process volumes. |
- Printing types are 1-pen, 2-pen, 6-dot, 12-dot types available.
|
- Wide applications for heat control in breweries, electric furnaces
|
and monitoring for process volume in industrial machinery |
|
Input |
: |
Thermocouple, RTD, DC Current, DC Voltage |
Number of input |
: |
1-pen, 2-pen (Pen writing), 6-point, 12-point (Dot printing type)
|
Indicating accuracy |
: |
Within ±0.5% of F.S. for both Thermocouple and RTD |
|
|
Within ±0.25% for DC Current and DC Voltage |
Recording speed |
: |
12.5, 25, 50, 100mm/h |
Printing interval |
: |
6 seconds/dot (50Hz), 5 seconds/dot (60Hz) |
Recording chart |
: |
Chart width; 180mm, Length 20m |
Recording method |
: |
Pen type; Ink pen continuous |
|
|
Dot printing type; Ink pad dot printing |
Power supply |
: |
1l0V, 115V, 120V, 130V & 140V (must be specified) AC
50/60Hz |
Options |
: |
High/Low limits alarm function, Controller parallel running
function |
Hybrid recorder |
HR-700
series |
[Features] |
 |
- Compact: 150mm in depth, 1.5kg in weight |
- RS-232C communication interface is provided as standard. |
- Large LED display with the size 18mm in height |
- IP65 structure allows usage in harsh environments such as |
food related plants, kiln. (Dust-proof, Drip-proof IEC529
IP65) |
|
Input |
: |
Thermocouple, RTD, DC Current, DC Voltage |
Number of input |
: |
1-pen, 2-pen (Pen writing), 6-point (Dot
printing) |
Digital accuracy rating |
|
±0.2%±1digit or less |
Recording accuracy |
: |
Measuring accuracy±(0.3% of recording span) |
Recording chart |
: |
Chart width; 100mm, Length 16m |
Printing method |
: |
Pen type; Disposable felt pen (1-pen red, 2-pen
green) |
|
|
Dot printing type; Wire dot (6-color ink ribbon) |
Recording period |
: |
Pen type; Continuous recording for each channel |
|
|
Dot printing type; Approx. 10 seconds (selectable from 10s,
20s, |
|
|
30s and 60s) |
Alarm function |
: |
Alarm output is not available. (The ALM indicator is
lit) |
|
|
(When alarm output is required, alarm output function
[option] is |
|
|
needed.) |
|
|
Alarm setting points; Max. 4 points (2 points each for high
limit and |
|
|
low limit) can be set per channel. |
Communication interface |
: |
RS-232C (1200/2400/4800/9600bps) |
Power supply |
: |
100 to 240V AC 50/60Hz |
Options |
: |
Communication function (RS-485), DI function,
Paper-empty |
|
|
detection function, Alarm output function |
Paperless
recorder |
GR-100
series |
[Features] |
 |
- Optimum screen can be selected from the Trend, Bargraph,
Data |
and Multi-screen according to the monitoring requirements.
|
- Continuous or intermittent input types can be selected
depending |
on the object being measured. |
- Measuring data can be stored up to max. 654000pcs. in the
|
internal memory of 1.25MB. |
|
Input |
: |
Thermocouple, RTD, DC Current, DC Voltage |
Number of input |
: |
Continuous input; 1-point, 2-point, 3-point, 4-point |
|
|
Intermittent input; 6-point |
Measuring cycle |
: |
Continuous input; Approx. 0.1 sec/4 points |
|
|
Intermittent input; Approx. 5 sec/6 points |
Indication screen |
: |
Trend, Bargraph, Multi-screen, Others |
Internal memory capacity |
: |
1.25MB |
Alarm function |
: |
Max. 4 points per channel can be set. |
Power supply |
: |
100 to 240V AC 50/60Hz |
Options |
: |
Alarm output/Remote contacts, Communication function, |
|
|
Mathematics, Integration, etc. |
|
|