Communication between (IFP-100)-(PROFIBUS master) |
Communication line |
: |
PROFIBUS(Based on RS-485) |
Communication speed |
: |
Automatically selected from
9.6k/19.2k/93.75k/187.5k/500k/ |
|
|
1.5M/3M/6M and 12Mbps. (Instrument with the lowest speed
|
|
|
connected on the same PROFIBUS line can automatically be
|
|
|
selected.) |
|
|
|
Communication between (IFP-100)-(Temperature
controller) |
Communication line |
: |
Based on RS-422A (RS-485) |
Communication speed |
: |
19.2kbps (Fixed) |
Data structure |
|
Start bit (1bit), Data bit (7bits), Parity (Even), Stop bit
(1bit) |
|
|
|
Setting |
: |
Self address of PROFIBUS communication can be set by a
rotary |
|
|
switch. Setting range is 0 to 99. |
Power supply |
: |
100 to 240V AC 50/60Hz,24V AC/DC 50/60Hz |
Power consumption |
: |
Approx. 2VA |
Insulation resistance |
: |
Between [Power terminal and controller communication
terminal], |
|
|
[Power terminal and PROFIBUS communication
terminal] |
|
|
10M ohm or greater, at 500V DC |
Case |
: |
Flame-resistant resin, Black |
Mounting |
: |
DIN rail mounting |
External dimensions |
: |
49(W) x 80(H) x 132(D)mm (including round type
socket) |
Weight |
: |
Approx. 200g |
|
|
|
- For a cable to connect IFP-100 with a PROFIBUS master
unit, use a cable and connector |
recommended by PROFIBUS association. |
For the web page of PROFIBUS association, please contact
www.profibus.com. |